On the network of cisco
module, We had a severe lightning storm with power cuts and multiple lightbolts
hitting our buildings and grounds around our core server rooms. Luckly the
UPSes carried the load and gobbled up the overvoltages etc no problem.
When checking the switch
I saw the following (see below), and even after running a "hw-module"
reset on each of the affected modules (blades) we still got no power (POE) to
the phones, however the computers directly connected were working fine.
Upon reseating or
resetting the module we got these errors on bootup of the module:
%PM_SCP-SP-2-LCP_FW_ERR_INFORM:
Module 6 is experiencing the following error: Inline Power Module - PS voltage
bad
%CONST_DIAG-SP-3-BOOTUP_TEST_FAIL:
Module 6: TestVDB failed
A "show module"
was showing this:
Mod Online Diag Status
---- -------------------
1 Pass
3 Pass
4 Pass
5 Pass
6
Minor Error
7
Minor Error
8
Minor Error
show diagnostic mod 7
Current bootup diagnostic
level: complete
Module 7: SFM-capable 48
port 10/100/1000mb RJ45 SerialNo :
xxxxxx
Overall Diagnostic Result for Module 7 :
MINOR ERROR
Diagnostic level at card bootup: complete
Test results: (. = Pass, F = Fail, U =
Untested)
1) TestLoopback:
Port
1 2 3
4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
24
----------------------------------------------------------------------------
.
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. .
Port 25 26 27 28 29 30 31 32 33 34 35 36 37
38 39 40 41 42 43 44 45 46 47 48
----------------------------------------------------------------------------
.
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. .
2) TestSynchedFabChannel -----------> .
3) TestL3VlanMet -------------------> .
4) TestIngressSpan -----------------> .
5) TestEgressSpan ------------------> .
6) TestAsicMemory ------------------> U
7) TestFirmwareDiagStatus ----------> .
8) TestEobcStressPing --------------> U
9) TestAsicSync --------------------> .
10) TestUnusedPortLoopback:
Port
1 2 3
4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
24
----------------------------------------------------------------------------
U
U U U
U U U
U U U
U U U
U U U
U U U
U U U
U U
Port 25 26 27 28 29 30 31 32 33 34 35 36 37
38 39 40 41 42 43 44 45 46 47 48
----------------------------------------------------------------------------
U
U U U
U U U
U U U
U U U
U U U
U U U
U U U
U U
11) TestErrorCounterMonitor ---------> .
12) TestIntPortLoopback -------------> .
13) TestPortTxMonitoring:
Port
1 2 3
4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
24
----------------------------------------------------------------------------
U
U U U
U U U
U U U
U U U
U U U
U U U
U U U
U U
Port 25 26 27 28 29 30 31 32 33 34 35 36 37
38 39 40 41 42 43 44 45 46 47 48
----------------------------------------------------------------------------
U
U U U
U U U
U U U
U U U
U U U
U U U
U U U
U U
14) TestVDB -------------------------> F
Basically from what I've
found the TESTVDB means that the POE component on the blade has failed, and it
will refuse to deliver power, at the time of writing this post, we don't know
whether the whole chassis is fried, we assume it isn't as all the other blades
and the data is working okay. And one of the other POE blades in the switch
survived and still delivers power.
Fault to Cisco, cross
fingers and hope the chassis isn't toast too.
Moral of the Story:
It doesn't matter how
much UPS protection you add a direct lightning strike will cause significant
damage and disruption to systems, the only protection you can have is to have
enough staff to deal with the problems, and enough money to fix or replace the
faulty kit.